The FR947-M PowerProbe was created to satisfy the rigorous fault recorder specification required by Enel S.p.A. LogicLab developed a high performance product, a digital fault recorder which defies comparison other ones you may find in the market.
Thirty-two (32) analog channels (voltage and current) noise-free and 128 digital inputs, give great potentialities and high precision acquisition. Every channel (analog or digital) is isolated from all other channels, the power-supply and ground.
The fault recorder is made for High Voltage/Medium Voltage (HV/MV) substations and is employed to record voltages and currents due to a trigger condition. This condition can be planned by users both on the analog inputs and digital ones. The fault recorder PowerProbe uses the GPS signal for time synchronization and events tag obtaining 1 microsecond of precision. Time synchronization options other then GPS are available.
The user, via Ethernet or RS232 connections, can perform remote parameterization and remote control of the equipment, recordings download by mean of a simple PC. Automatic recording download makes it possible to transfer recording directly on PC mass storage memory. FR947-M is in every case equipped with flash memory that allows to do non-volatile recording up to 250 seconds.
The digital fault recorder FR947-M PowerProbe is provided with two easy-use software programs that allow a complete management of the device, useful recording downloading and monitoring, as well as an effective and powerful analysis system.
LogicLab also offers a smaller, less expensive solution with that fits in a 3U rack-mount panel. Configurations with up to 16 analog input and 32 digital input are available. Other hardware and software is available for these devices including an HMI interface, Digital Output, Multiple Time Synchronization, 100BASE-FX interface. Please refer to Optional section at Technical information page in brochure that you can download at this web page.
Technical page:
Fault Recorder (or Digital Fault Recorder)
View the product brochure:
[English: http://www.logiclab.it/Documents/Fault%20recorder%20LogicLab.pdf] [Italian: http://www.logiclab.it/Documents/BrochureOscilloperturbografo.pdf]
Website:
http://www.logiclab.it (english site): http://www.logiclab.it/en/DV947.htm (italian site): http://www.logiclab.it/it/DV947.htm
RTEMS LogicLab page:
Other LogicLab Fault Recorder:
Digital Fault Recorder with Phasor Measurement Unit Description: FR947-PMU Technical data: Fault Recorder with PMU
Other LogicLab Applications
DV938EAC - Automatic Load Shed Description: DV938EAC Automatic Load Shed Technical data: Automatic Load Shed